From now on, the electrical accreditation is a regulatory requirement for those who act on electrical installations or near these installations. It requires a previous training.

It consists in the recognition, from his/her employer, of the hability of an individual to perform safely his/her duties. 
The accreditation is not directly linked to the hierarchical position nor the occupational classification. 
The accreditation is embodied by a document provided by the employer and both signed up by the employer and the accreditated individual.

Providing an accreditation does not exempt the employer from his/her responsibility.

The sole accreditation does not allow its holder to perform by himself/herself operations for which he/she is accreditated. 
His/her employer has to appoint him/her to perform these operations. The placement in a job position can constitute an implicit appointment.

This accreditation recognition requires:

  • knowing and preparing assigned duties, taking into account the status of the installation
  • respecting the conditions listed in the following chapter.

Are concerned all the workers directly or indireclty exposed to the electrical risks.

Electricity is invisible and is often presented in a complicated way.
It is difficult to grasp it safely without being trained.
Electricity-related accident data are particular (few accidents but often lethal).

Number of electricity-related accidents at work (with lost time incidence)

 

Number of PD (Permanent Disabilities) and number of deaths

 

Accidents at work in 2006

One will note the greater percent of deaths following an electricity-related accident at work than all the accidents at work.
Every year, 4% of the workers are victims of an accident at work.

Electricity-related accident according to CTN

CTN = French technical Comittee

AW - LTI

AW - PD

Death

A  Metallurgy

150

5

0

B  Building and public works

258

34

7

C  Transports, Water-Gas-Electricity, Book, Communication

61

4

0

D  Food

97

7

1

E  Chemistry, Rubber, Plastification

30

3

1

F  Wood, Furnishing, Paper-cardboard, Textiles, Garments…

31

2

0

G  Non-food stores

53

4

1

H  Service activities I

35

2

0

I    Service activities II and temporary Work

119

13

1

Electricity total

834

74

11

All accidents at work

700,772

46,596

537

Percent of electricity-related accidents

0.12%

0.16%

2.05%

AW > Accident at work  /  LTI > Lost Time Incidence  /  PD > Permanent Disability

 

Origins of the Accidents at Work in 2007

On constate :

  • Electricity-related accident at work constitutes: 838/720150 = 1.2 for 1000 of all the accidents at work
  • Electricity-related accident at work constitutes: 11/622 = 18 deaths for 1000 accidents

Main causes of accident

Cause

AW-LTI

AW-PD

Death

# TD days

Accident on the level

170,762

10,535

16

8,952,240

Fall from an height

87,656

7,813

88

6,320,781

Manual handling

249,778

14,388

17

11,567,566

Moving mass

42,412

2,120

40

1,449,507

Lifting

24,686

1,595

24

1,277,245

Vehicles

22,186

2,418

144

1,520,422

Machines

21,911

2,243

10

888,213

Earthmoving machines

1,026

153

14

81,457

Tools

47,474

1,899

0

1,175,810

Electricity

838

86

11

42,766

Various devices

10,273

384

5

246,584

Others

41,148

2,792

253

2,348,550

Total

720,150

46,426

622

35,871,141

AW > Accident at work  /  LTI > Lost Time Incidence  /  PD > Permanent Disability  /  TD > Temporary Disability

 

In other words:

1000 Accidents at work (any causes) 1000 Electricity-related accidents at work
64 Permanent disabilities 102 Permanent disabilities
1 Death 13 Deaths

ELECTRICITY IS 13 TIMES MORE LETHAL
than the main causes of accidents at work

 

Main accident occurrence conditions:

Electric shock condition % Most concerned staff
Live working 36 Electricians
Installations in poor conditions 30 Users (Operators)
Hand-held device 14 Maintenance mechanics
On low-voltage installations 3 Vehicle mechanics
No precise cause 17  

 

Activities and operation types

Workers

Symbol

ACFITEC training duration

No electricity-related operation is performed but access to areas or places presenting a specific electrical risk (access restricted to electricians).

 

Painter, mason, locksmith, cleaning agent... that do not set up the circuit breaker, nor replace lamps, fuses… but only performs painting, masonry works (for instance: taking pictures, reading meters, etc)

 

B0

H0

H0V

1 DAY

Basic intervention on terminal circuits (maxi 400V and 32A alternating current).

Operation types:

- replacing and installing water heaters, convectors, rolling shutters, heating circulator pumps, etc.

- replacing LT fuses, reseting protection

- replacing by an identical lamp, a socket outlet, a switch

- connecting on waiting terminal boxes (connector boxes, …)

- setting up a protection device

 

Building manager,
heating engineer, plumber, painter, …

BS

BP

2 DAYS

Maneuvering electrical materials to reset a circuit breaker, thermal relays,…

Turning on/off a device, an installation

Computer operator, keeper, production staff performing only this type of maneuver

 

BE Maneuver

2 DAYS

General cleaning and troubleshooting on circuits (maxi 1000V and 63A alternating current).

Operation types:

- finding failures, malfunctionings

- performing measurements, tests, maneuvers

- replacing defective equipments (relays, terminal boxes, …)

- partially and temporarily commissioning an installation

- connecting and disconnecting in presence of voltage (maxi 500V in alternating current)

 

Skilled electrician of the maintenance service,
repair man, etc

BR

3 DAYS

Works (new) on electrical structures and installations.

 

Operation types:

- creating, modificating an electrical installation

- replacing a switch box, an electrical cabine

- marking the working area, supervision of the electrician staff, checking of the proper completion of work (only for the manager), etc.

 

 

Performer:

B1, H1

 

Manager:

B2, H2

3 DAYS Low Voltage

+ 1 DAY High Voltage

Locking out an electrical structure or installation in low or high voltage.

 

 

BC, HC

3 DAYS

Installing photovoltaics

 

 

BP

2 DAYS

Other operations of the test, check, measurement type on electrical material.

 

 

BE Test, BE Measurement, BE Check

3 DAYS

Responsibility of the different stakeholders

The legal responsibility and critical thinking about safety

Whatever are the legal responsibilities of each stakeholder, and their wish to respect the rules (from the safety point of view), each one personally guarantees his/her own security.  

One must have a critical thinking about safety in order to properly face working situations in which safety prescriptions are threatened. 


PPEs (Personal Protection Equipments) 

Responsibility consisting in maintaining PPEs (and tools)  in good condition:

  • the operator and the work supervisor

Responsibility of the condition and wearing of the PPEs:

  • the accreditated individual

 

The right to withdraw

Any employee (or group of employees) being in a working situation for which he/she has reasonable grounds to think that it presents a serious and imminent risk for his/her life or health, can notify the employer and remove himself/hersel from this situation, making sure not to create a new situation of serious and imminent risk for others.

 

Responsibility of the manager in case of subcontracting

Case of external companies 

When the employer assigns electrical works to external companies, he has to make sure that they are qualified, that is:

  • they are registered in the commercial register and trades register as electrical work companies or they have the specific services responsible for the provision and maintenance of the material electrical equipments they manufacture or install,
  • their employees have been trained in the knowledge of the electrical risks and means to protect themselves and possess a relevant accreditation title, provided by the external company.

It is also mandatory, whatever the work duration, for the user company and the external company operating consult in order to protect oneself against all risks, resulting from their co-activity, including the electrical risk. 


Case of agency temporary staff 

The user manager of the company has, when calling on agency temporary staff:

  • to check that the staff has obtained the required training for performing electrical or non-electrical duties they will be assigned,
  • or to provide hem this training, in order to accreditate them.

The NFC18-510 (electrical accreditation) training does not consitute by itself the reinforced training. 

The company will have to organize the practice training of the temporary agency on the company installations or similar installations.  

In practical terms, the use of a temporary employee requires the following documents:

  • a mission request form provided by the user company indicating: the employee desired professionnal skills (required accreditation),
  • a form to be fulfilled by the temporary work agency (TWA) and aiming at providing all usefull information (training, already performed operations, previously obtained accreditations...) to the user company for accreditation. This document shall make it possible to check, notably, if the proposed employee has attended or not the accreditation initial training.  


It should be emphasized the following:

  • this training aiming at upgrading the general theorical knowledge in terms of security, does not exempt the user company:
    • to check the knowledge of the agency temporary employee,
    • to provide the employee the reception and required training to adapt to the workstation,
    • to check that the agency temporary employee possess the prescription note based on the UTE C 18-510.
  • the accreditation is provided by the user company solely for the mission assigned to the temporary employee.

Normal periodicity

The refresher training is to be provided at a periodicity to be defined according to the performed duties:

  • operation complexity, or frequency,
  • material technological evolution,
  • diversity (for instance: external company agent).

The suggested periodicity is of 3 years, this periodicity will be notified by the employer. An annual check of the accreditation levels is recommended.
For live workings, the title is valid for 1 year.

Particular case

A refresher training is to be planned in the following cases:

  • at any change of the duties,
  • at any structure modification of the electric power supply and distribution network, in the case of a one company permanent staff.

Technical qualification

This qualification is required to provide a quality work and to safely perform the duties.

Medical fitness

Any employee has to possess a certificate of fitness to perform the assigned duties, provided by the occupational physician in the general course of the regulatory inspections (Labour Code).
To do so, the occupational physician will be notified, if applicable, of the electricity-related duties assigned to the employees so that he/she can adapt, by himself, the considered useful medical exams.

From among the recommended exams, the following can be mentioned:

  • colour vision trouble screening,
  • movement coordination for individuals to be R, V, N or T accreditated
  • and electrocardiogram.

Electrical safety training

Theoretical training 
The UTE C 18-510 booklet contains the requisite elements for this training. However, the later has to adapt to:

  • the installation features (complexity, variability),
  • the initial skills and future attributions of the staff to be accreditated.

To this end, a previous analyze of the company needs is necessary to precisely define the required grade(s) of accreditation.

The content of the training model previously proposed can be optimized:

  • bearing in mind the trainee level,
  • and the company objectives,

after opinion of a qualified individual and in particular:

  • from the trainer, after installation inspection in case of intra-company training,
  • members of the CHSCT (French health, safety and working conditions comittee).

Practice training

  • Put into practice of the gained theoretical knowledge, if possible on the company installation, or on similar installations,
  • Reminder of the installation features and of the used material.

Training certificate

At the end of the training, the trainee will receive, from the trainer, a certificate in which will be mentioned in particular:

  • the trainee's name and forename,
  • the type of training and its actual duration,
  • the success or failure of the trainee at the end of the final duration, explicitly mentioned

The trainer will give the employer an opinion helping him to define the content of the accreditation title according to the performed work and will precise the evaluation criteria.

Additional training

In case of accreditation grade change, an additional training corresponding to the required grade will be necessary.

Providing of the accreditation title

The accreditation title is provided by the employer according to:

  • the technical knowledge of the individual to be accreditated,
  • the medical fitness of the individual to be accreditated,
  • the trainer certificate.

In the accreditation title, are to be defined:

  • the accreditation grade,
  • the authorized duties,
  • the authorized geographical areas, installations or/and yards.

It also necessarily includes:

  • information concerning the identity of the employer and his/her signature,
  • information concerning the identity of the title holder and his/her signature,
  • the notification of the accreditation delivery date,
  • the accreditation validity duration.

The content of the title will comply with the model presented in the UTE C18-510 booklet.
The employer will give the employee the prescription book based on the UTE C 18-510 booklet.

Practice experience

It is recommended, within a short time period after delivery of the accreditation title, for the company permanent staff, to perform the duties assigned by his/her employer with the accompanying of a skilled and accreditated individual (at a sufficient grade).

This period duration, defined by the business manager, shall be adapted to the complexity of the installations, the qualification, the professional experience of the staff.

For temporary staff, this duration matches the practice experience gained during different missions on similar installations.

Very important: 

In case of live working, a specific training has to be provided by a body recognied by the French Live working comitee "Comité des travaux sous tension" (EDF, Délégation à la prévention et à la gestion des risques, 54 avenue Robert-Schuman, BP 1246, 68054 Mulhouse cedex, FRANCE. Tel. : +33 (0)3 89 35 22 04).

The intervention methods have to be defined and a relevant material provided.

The employer has to ensure that his/her staff still have the required knowledge and skills to perform safely the assigned duties. The NFC 18-510 calls for a refresher every 3 years. The electrical accreditation refresher aims to refresh and even complete the staff knowledge and know-how. However, this recommendation can be reduced to 2 years in the case of a casual or exceptional practice.

Every year, has to follow up and ensure that his/her employee electrical accreditations comply with the foreseable developments of the operations performed by his/her staff or the installations handled by the same. If it is not compliant, the employer can:
- return to a duty complying with the electrical accreditation held by his/her staff;
- reassign the duty to a worker holding the corresponding electrical accreditation;
- complete his/her employee training so that he/she has the requisite skills to perform the duty and modify his/her title.

In specific cases, a refresher training is necessary, such as:
- if the employer notes a non-respect of the safey procedures due to a lack of knowledge;
- the development of the workin methods;
- the cessation of the operations for 6 months at least;
- the technological evolution of the materials;
- the evolution of the regulation.

BE CAREFUL! A refresher training does not allow to raise the initial electrical accreditation grade, it has to be presented to te trainer at te begining of the training.

Click on the following link and enter our form to send us your request..

Call Us

+33(0)4 42 92 86 31

OR

Enter your telephone number, we call you back within an hour.

Open from Monday to Friday
from 9:00 AM to 5:30 PM

Calendar of the trainings per city
Paris
Aix en Provence
Bordeaux
Lyon
Nancy
Rennes
Toulouse

See the calendar of our electrical accreditation trainings.